Solution
VES utilised their expertise, offering unique insights into improving air quality, the building operation and environmental impact and proposed refurbishing the existing AHU.
VES identified that the maximum possible duty the existing unit was capable of achieving was 10.7 m³/s due to maximum velocity limitations over the existing components. VES proposed 5no EC plug fans to work simultaneously in a fan wall to achieve the new increased design duty.
The heating and cooling coils were in poor condition and therefore replaced to suit the new design air volume. Due to the restricted access and existing pipe work connections, the coils were supplied in 2 sections. The fresh air inlet damper was replaced, and the panel and bag filters were upgraded along with the filter frame to suit the new air volume.